Diesel generator maintenance
Check firewood hair units overall appearance of the situation, the need to clean any possible leakage, oil leakage, base mounting bolts and other bolts fastening, if abnormal timely.
Flammable lightweight items, check the the diesel generators ventilation channels shall not be stacked to prevent fires and involvement of foreign body accident.
Check engine room fire extinguishers on the location of its provisions.
Check into the exhaust louvers can smoothly open.
Check the cooling fan belt tension and wear conditions, if necessary, adjust or replace.
Check the hose connection and hose appears to replace the aging cracking, as the case.
In case of cooler groups, Check the intercooler connection hoses for leaks or cracks, as the case replacement appears.
Check the coolant level is normal, coolant replaced every two years.
Check the generator and the circulating pump of the belt tension and the degree of wear and, if necessary, adjustment or replacement.
Check electrolyte level start battery each Cell, such as below the standard you need to add.
Check the starter battery charger working status is normal and measure the float voltage, record.
Check the battery and starter connections cable connector fastening, tightening necessary.
Check the diesel tank of diesel reserves, and check magnetic oil level the ruler measurement accuracy, whether the the communicating vessel type scale check valve leaked.
Depending on the amount of fuel annually how to determine a few years time the fuel tank of sewage and oil filter cleaning or replacement.
If any two diesel transfer pump, check the pump control system and pump seal condition.
According to the history of the diesel generator run time and standby time to determine when to replace the diesel filter. And to record replacement time and more run time when firewood hair.
Check the oil-water separator sediment and regular drainage.
Check the speed limiter in good condition.
Check the fuel pump is in good condition.
Determined in accordance with the cleanliness of the running time of the diesel generator and diesel engine room when the air filter needs to be replaced. And record the time for replacement and replacement of the running time of the Cai hair.
Each inspection to check the oil level and color.
Fully synthetic or semi-synthetic to determine whether the diesel generator run time and standby time, and lubricating oil need to replace the oil, change the oil and replace the oil filter. Firewood hair run time and change the oil brand label and record the time for replacement and replacement.
Check the exhaust pipe connections for loose insulation is good.
Check muffler coke and puddles.
Health check-start device is normal.
Check the diesel generator control system and indicating instrument and signal lights are normal.
Check the electric ball cooling channel non-blocking.
The degree of tightening of the check the power cable connection terminal, if necessary, fastening.
After the adoption of the above checks,, recommended monthly simulate a mains power failure from the start (or hand start) diesel generators, but pay attention to the ATS switch Do not let ATS Go firewood hair side powered, unless doing annual simulated load test before allowing ATS to go to the diesel generator side of the power supply.
Maintenance personnel need good insulation protection, noise protection, eye protection, clothing to wear to avoid getting involved.